Cooper-instruments-systems DFI INFINITY Digital Force Indicator/Controller Manual de usuario

Busca en linea o descarga Manual de usuario para Instrumentos de medición Cooper-instruments-systems DFI INFINITY Digital Force Indicator/Controller. Cooper Instruments & Systems DFI INFINITY Digital Force Indicator/Controller User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 78
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
DFI INFINITY
SERIAL COMMUNICATIONS GUIDE
www.cooperinstruments.com
PH: 540-349-4746 FAX: 540-347-4755
Vista de pagina 0
1 2 3 4 5 6 ... 77 78

Indice de contenidos

Pagina 1 - SERIAL COMMUNICATIONS GUIDE

DFI INFINITY SERIAL COMMUNICATIONS GUIDE www.cooperinstruments.com PH: 540-349-4746 • FAX: 540-347-47

Pagina 2 - TABLE OF CONTENTS

Logic symbols are opto-isolated, and drive power is obtained from a galvanically-isolated transformer winding so that the differential signals (minimu

Pagina 3

Table 2.4. Full-Duplex Hookup to the Computer METER (DCE) RJ-12 NEW OLDER PIN SIGNAL/ FUNCTION RS-485 RS-485 BD COMPUTER (DTE) D9/D25 +TX 1 1 (SE

Pagina 4

Pressing the ‘MENU’ button saves your choices and advances to “ADDRES”. This is used to set in an RS-485 device from address 0 to 199 and is accompl

Pagina 5 - 2. HARDWARE

4.7 Full Duplex Two channels (e.g., two twisted pairs) with bi-directional data flow at any time (one simplex channel in each direction). 4.8 RS-232

Pagina 6

To make the best use of the available storage, all possible bit sequences should be used, so each nibble can have 16 different values (not just the te

Pagina 7

Table 4.2 Meter Receiving Voltages OPTION TYPE “1” BIT/MARK OR STOP BIT “0” BIT/SPACE OR START BIT RS-232 RS-422 OR 485 -3 > A > -15 V A< (B

Pagina 8 - 2.3 RS-485 Hardware

Figure 6-1. Character Waveform The rising edge of the start bit of the next character may occur at any time after the end of the last stop bit. 7

Pagina 9

7.2 Multipoint A device address from 0 to 199 is included in the COMMAND or RESPONSE message. By using the addressing capabilities, collision on the

Pagina 10

7.4 The Meter As A Double Tasking Remote Meter The Process, Strain Gauge, Temperature and Universal meters can be configured as a double tasking remo

Pagina 11

8. COMMAND AND RESPONSE STRUCTURE 8.1 Message String 8.1.1 “Data” and “Non Data” Each of the many types of messages between computer or printer and t

Pagina 12 - 4. DEFINITIONS

TABLE OF CONTENTS 1. INTRODUCTION ...

Pagina 13

where nn = device address from 01 to C7 (hex) = 01 to 199 decimal. NOTE: Response detail is given in Section 8.8 and 8.9. 8.2.2 General Command Str

Pagina 14

b) Multipoint mode: *nnccc[hh]<CR> For “Y” Command (Process, Strain Gauge, Temperature and Universal meters only): Remote Display a) Point-to

Pagina 15 - 6. CHARACTER WAVEFORM

Command Suffix Item affected #Char Section V 01 Read data string 0 8.2.3 X 01 Read unfiltered value 0 8.2.3 Y 01 Write value to display 6

Pagina 16 - 7. CLASSES OF OPERATION

Command Suffix Item affected #Char Section G, P, R, W 40 RAM or EEPROM BLOCK A 60 10.25.1 G, P, R, W 41 RAM or EEPROM BLOCK B 38 10.25.2 R,

Pagina 17 - 7.2.2 Alarm Mode

COMMAND SUFFIX ITEM AFFECTED # CHAR SECTION E 04 Set alarm mode - 7.2.2 G,P,R,W 04 Setpoint 4 value 6 11.16 X 04 Read time value 8 8.2.3 Z

Pagina 18

COMMAND SUFFIX ITEM AFFECTED # CHAR SECTION G,P 41 RAM Block B Batch and (SQ RT): 34 Rate:36 11.32 R,W 41 EEPROM Block B Batch and (SQ RT): 50 R

Pagina 19 - 8.2 Commands and Structure

2. Suffixes 0E and 0F are not used: the meter will respond to these with an error message. 3. The meter, upon completion of a BLOCK PUT (into RAM) Co

Pagina 20 - 8.2.3 Command Formats

2) For the Rate meter/totalizer or Batch meters: [Sa][S<value>][SP<uuu>][S<value>][SP<uuu>][S<value>][SP<uuu>][S&l

Pagina 21 - 8.2.4 Command Suffix

?ee<CR>[<LF>] where “?ee” is the special code indicating an error has occurred as follows: 8.5.2 Error Message Table 8.4 Error messages

Pagina 22

2. When in multipoint mode, the meter will test the command’s address with the one previously assigned after the recognition character has been match

Pagina 23

8.5.1 Error Response Format... 23 8.5.2 Error

Pagina 24

CHARACTER SP#5 SP#4 SP#3 SP#2 SP#1 M OFF ON ON OFF ON N OFF ON ON ON OFF O OFF ON ON ON ON P ON OFF OFF OFF OFF Q ON OFF OFF OFF ON R

Pagina 25

Table 8.8 Description of Special Characters Used for Communication Commands CHARACTERS PROCESS, STRAIN GAUGE, TEMP., UNIVERSAL METER RATE/SQ METER B

Pagina 26 - 8.3.3 No Echo Mode

Command format *15G1A<CR> Response format 15G1A15<CR> 3. Write “VLT” as units of measure into the EEPROM of the meter in the point-

Pagina 27 - 8.5.1 Error Response Format

c) meter’s address is “15 HEX” if it is used in the multipoint mode d) no line feed or checksum characters are included 1. Read serial recognition

Pagina 28 - 8.5.3 Description

10. Read block of data from EEPROM in point-to-point mode when the meter is operating in Batch Mode: Command format *R42<CR> Response forma

Pagina 29

1. For Process, Strain Gauge, Temperature and Universal meters: a) Slow mode = 0 to 300 ms b) Fast mode = 0 to 100 ms 2. For Ratemeter/totalizer,

Pagina 30

transmission. Specifically, if command “^AE” is transmitted, it will cause the meter to switch to COMMAND mode. To be able to communicate with the m

Pagina 31 - 8.8 “^AE” Response Format

To use this command for the Process, Strain Gauge, Temperature or Universal meters, bit “BUS.8” must “=1” (Refer to Section 10.23). To use this comm

Pagina 32

3. When “W” command is given, a reset is necessary to initiate the command. 4. “X” in bit pattern information means the bit is not related to that par

Pagina 33

LOCKOUT FUNCTION CORRESPONDING ITEM =1 Locked L2C.8=0 =1 Unlocked Locked FIL.CNF: Filter Configuration L3 CNF: LOCKOUT CONFIG

Pagina 34 - 9. METER BUS RESPONSE

11.3 Display Mode ...54 11.

Pagina 35 - 9.2.1 Meter’s Response Time

Table 10.3. Input Range for Thermocouple BIT NUMBER 3 2 1 0 RANGE OR TYPE 0 0 0 0 J 0 0 0 1 K 1 0 1 0 T 0 0 1 1 E 0 1 0 0 N 0 1 0 1 DIN J 0 1

Pagina 36 - 9.4 External Print Command

10.3 Reading Configuration (“RDG.CNF”) 2 Characters (2 nibbles) of data are used for all four 07 commands: Table 10.6. Reading Configuration (“RDG.CN

Pagina 37 - 9.4.1 Meter’s Response Time

SC=(O2-O1)/(I2-I1) This value is entered/read with these “08”, 0B” and “17” command suffixes, and also used in calculating the corresponding Offsets

Pagina 38 - 10.1 Lockout Bytes

MSN are used for decimal point (referenced to the right-hand display dp position) as given in the Table 10.10. The remaining 5 nibbles (20 bits) are

Pagina 39 - 10.2 Input Type (“Input”)

Table 10.12 Input Configuration (“IN CNF”), Bits 4, and 3 BIT NUMBER 4 3 FUNCTION (VALID IN RTD OR TC MODES) 0 0 No transmitter 0 1 TC Transmitter

Pagina 40

EXAMPLE: The computer wants to set meter #15 hex to center the decimal point and count-by-10. It transmits “*15P0C43<CR>”. These data are put

Pagina 41

Table 10.18. Setpoint 1 Configuration (“SP CNF”), Bits 2, 1, and 0 BIT NUMBER 2 1 0 CONFIGURATION x x 0 SP 1 active above x x 1 SP 1 active belo

Pagina 42

Table 10.22. Alarm 2 (SP 4) Configuration (“AL CNF”), Bits 5, 4, and 3 BIT NUMBER 4 3 CONFIGURATION x 0 AL 2 (SP 4) active above 5 x x x 1 AL 2

Pagina 43

Table 10.26. Alarm 1 and 2 Delay BIT NUMBER 3/7 2/6 1/5 0/4 # OF ALARMS BEFORE ALARM IS ACTIVE 0 0 0 0 0 0 0 0 1 1 0 0 1 0 2 0 0 1 1 3 0 1 0

Pagina 44

Table 10.27. Output Configuration (“OUT.CNF”) Bits 4, 3, 2, 1, and 0 BIT NUMBERS 4 3 2 1 0 SELECTS x x x x 0 Analog output disabled x x x x

Pagina 45

1. INTRODUCTION This guide is intended to facilitate digital communication between your computer (or other controlling device) and one or more meters.

Pagina 46

Table 10.30. Serial Configuration (“SER.CNF”) Bits 7,6 5, and 4 BIT NUMBER 7 6 5 4 ALARM 2 (SP 4) CONFIGURATION x x 0 0 No parity (automatically

Pagina 47

Table 10.32. Data Format (“DAT FT”), Bits 7, 6, 5, and 4 BIT NUMBER 7 6 5 4 SELECTS x x x 0 Don’t send PEAK value x x x 1 Send PEAK x x 0 x D

Pagina 48

Table 10.35. Bus Format (“BUS FT”), Bits 7 and 6 BIT NUMBER 7 6 FUNCTION x 0 RS-485 board not installed x 1 RS-485 board installed 0 x External

Pagina 49

Each letter is represented by the two HEX-ASCII characters giving its ASCII table address, from “41” to 79” (all upper and lower case letters) or the

Pagina 50 - 10.17 RS-485 Meter “ADDRES”

Table 10.37. Setpoint Values, Bits 23, 22, 21, and 20 BIT PATTERN 23 22 21 20 SIGN AND DECIMAL POINT 0 0 0 0 0 0 +FFFFFF. 0 0 1 0 +FFFFF.F 0 0 1 1 +

Pagina 51

NOTE: R, W means “R” or “W” 10.25.1 BLOCK A This block consists of ten (10) items and thirty bytes (60 ASCII characters) as Table 10.39: Table 10.39.

Pagina 52 - 10.22 Units Of Measure

10.25.4 EXAMPLE: Assuming echo mode; no line feed; checksum; and point-to-point mode. 1. Read Block C from EEPROM a) And send to the meter: *R42<

Pagina 53

Table 11.1. Lockouts LOCKOUT FUNCTION CORRESPONDING ITEM L1 CNF: LOCKOUT CONFIGURATION #1 L1C.1=0 =1 Unlocked Locked Display of Setpoint

Pagina 54 - 10.25 Block Read or Write

11.2 Mode Mode is one byte of data (2 characters). It uses the prefixes G, R, and W with the suffix 07. This byte controls the operating mode of the

Pagina 55 - 10.25.3 BLOCK C

11.4 Configuration 1 (“CNFG 1”) This item is 1 byte (2 characters). It uses command prefixes G, P, R, and W with the suffix 0A. The bit pattern is

Pagina 56 - 10.25.4 EXAMPLE:

Figure 2-1A. RS-232 Option Board Figure 2-1B Older RS-232 Option Board Refer to Figure 2-1B. When interfacing the meter to devices that do not ha

Pagina 57

FUNCTION BIT NO. VALUE RATE AND SQ RT MODES BATCH MODE 3 0 1 SP 4 is active above SP 4 is active below 4 0 1 SP 5 is active above SP 5 is active be

Pagina 58 - 11.3 Display Mode

Table 11.6. Configuration 3 (“CNFG 3”), Byte 2 FUNCTION BIT NO. VALUE RATE AND SQ RT MODES BATCH MODE 0-1 0 SP 1 output is normal (unlatched) 1

Pagina 59

To write these values to RAM of meter #15, send the command *15P0C31C814<CR>. The meter will respond with 15P0C<CR>. 11.7 Configuratio

Pagina 60

Table 11.9. Average Configuration (“AVG.CNF”) Bits 3-0 BIT NUMBER 3 2 1 0 NO. OF READINGS IN AVERAGING 0 0 0 0 1 0 0 0 1 2 0 0 1 0 4 0 0 1 1

Pagina 61

Table 11.12. Pulsed Setpoint Values VALUE RESULT 0 AL TI is used for analog output ramping function 1 AL TI pertains to Setpoint 1 2 AL TI pertain

Pagina 62

For example, you want your input scale to be 15.25. This equals a squared value of 232.5625. The value excluding the decimal point is larger than 10

Pagina 63

Table 11.14 shows the decimal point value based on the decimal no.: Table 11.14. Decimal Point Values DP VALUE DECIMAL NO. (POWER OF 10 MULTIPLIER)

Pagina 64 - 11.11 Alarm Time (“AL TI”)

TOTAL Reading = (Raw Total) * (TOT SC) + TOT OF RATE Reading = (Raw Rate) * (RTE SC) + RTE OF BATCH Count Reading = (Raw_Batch_Count) * (BAT SC) + B L

Pagina 65 - (“TOT DP”)

11.18 Set Time (“SET TI”) This item is a special 3-byte value in Hex format. It sets the time on the display when the front-panel RESET button or th

Pagina 66

11.20 Output Offset This item is 3 bytes (6 characters). It uses the prefixes G, P, R and W with the suffix 27. Bits 0 through 19 assign the value.

Pagina 67 - 11.15 Scale Operator

Figure 2-3. Rear of Meter with J4 Connection Figures 2-4A and Figure 2-4B show the four-wire RS-232 connections between the host computer/controller

Pagina 68 - 11.19 Output Scale

Byte 1 (Least) = seconds, Max 59 Byte 2 (Middle) = minutes, Max 59 Byte 3 (Most) = hours, Max 99 EXAMPLE: You want to assign TIME of meter #15 to 7:

Pagina 69 - And Time

Table 11.21. Serial Configuration (“SER.CNF”) Bits BIT NO. VALUE FUNCTION 0 0 1 1 Stop bit 2 Stop bits 1-2 0 1 2 3 No parity Odd parity Even parit

Pagina 70 - 11.22 Baud Rate (“BAUD”)

These settings correspond to binary 00101011 = 2B Hex. Send the command *15P1B2B<CR>. The meter will respond with 151B<CR>. 11.25 Comm

Pagina 71

Table 11.24. Serial Time (“SER TI”) Values VALUE FUNCTION 0 Transmit at each reading cycle 1 to 59999 (decimal) Transmit using this interval (in se

Pagina 72

11.31 Calibration Items a) Analog Output. These items are each 2-byte Hex values (4 characters), that are on the back of the isolated analog output b

Pagina 73 - 11.29 Units Of Measure

11.32.1 Block A (For G, P, R, W Commands) This block has different data length depending on meter’s mode. It consists of eighteen (18) items and th

Pagina 74 - 11.32 Block Read Or Write

Table 11.29. Block B for “G” or “P” Commands For Batch or Square-root Modes ITEM (HEX) SUFFIX DESCRIPTION BYTE NO. & ORDER 25 Serial delay 1 24

Pagina 75

Command Prefix: “R” and “W”. It consists of 16 items, 26 bytes (52 ASCII characters) as shown in Table 11.32. Table 11.32. Block B for “R” or “W” C

Pagina 76

CF 125 INFINITY SC GUIDE 74 M1519/N/0605 Table 11.34. Block E For “P” and “W” Prefix Commands For the Batch meter, Square-root and Rate Modes ITEM

Pagina 77

Table 2.1. Meter Hookup (RS-232) to the Computer METER (DCE) COMPUTER (DTE) PIN SIGNAL/ FUNCTION RJ-11 RJ-12 D9 D25 RTS, meter from computer 1 2

Pagina 78 - 11.32.7 Example

JUMPER RS485 HALF DUPLEX RS485 FULL DUPLEX (CLOSE FOR TERMINAL RESISTOR) S3-B CLOSE OPEN S3-C (CLOSE FOR TERMINAL RESISTOR) * * S3-D CLOSE OPEN S3-E (